RXT Series Packaged Water-to-Air
Multi-Positional Heat Pumps
Engineering Data and
Installation Manual
Table of Contents:
Section 1: Model Nomenclature
Model Nomenclature ..............................................................2
Section 2: AHRI Performance Data
Performance Data...................................................................3
Section 3: Unit Dimensional and Physical Data
Unit Dimensional Data .............................................................4
Unit Physical Data ....................................................................5
Section 4: Electrical Data
Unit Electrical Data ..................................................................6
Section 5: Speci cation Glossary & Calculations
Glossary & Flow Rate Calculations ........................................7
Section 6: Unit Performance Data
Extended Unit Performance Data ..................................8 - 17
Performance Data Correction Factors ...............................18
Section 7: Installation Introduction
Introduction, Pre-Installation, Components .................19 - 20
Section 8: Installation Considerations
Installation Considerations ....................................................21
Section 9: Installation
Unit Placement .......................................................................22
Unit Conversion ......................................................................23
Ductwork Installation ......................................................24 - 25
Section 10: Unit Piping Installation
Interior Piping, Water Quality .........................................26 - 30
Section 11: Antifreeze
Overview ................................................................................. 31
Antifreeze Charging .......................................................32 - 33
Section 12: Desuperheater Installation
Installation ........................................................................34 - 36
Section 13: Controls
Controls & Wiring Diagrams ...........................................37 - 42
Section 14: Accessories
Auxiliary Electric Heat ............................................................43
APSMA Pump Sharing Module .............................................44
Section 15: Troubleshooting
Troubleshooting ...............................................................45 - 49
Section 16: Forms
Troubleshooting, Unit Start-Up .........................................51, 53
Section 17: Warranty
Warranty ...........................................................................55 - 56
Guide Revision Table:
Date By Page Note
14 Nov 2011 DS All First published
Roth is continually working to improve its products. As a
result, the design and speci cations of each product may
change without notice and may not be as described
herein. For the most up-to-date information, please visit
our website, or contact our Customer Service department
at [email protected]. Statements and other information
contained herein are not express warranties and do not
form the basis of any bargain between the parties, but are
merely Roth’s opinion or commendation of its products.
© Roth, 2011
P.O. Box 245
Syracuse, NY 13211
www.roth-usa.com
888-266-7684
Page view 0
1 2 3 4 5 6 ... 55 56

Summary of Contents

Page 1 - Installation Manual

RXT Series Packaged Water-to-Air Multi-Positional Heat PumpsEngineering Data andInstallation ManualTable of Contents:Section 1: Model NomenclatureMod

Page 2 - Section 1: Model Nomenclature

10Roth RXT Series, 14 Nov 2011DHeating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 18 for different condit

Page 3 - Ground Water Heat Pump

11RXT Series, 14 Nov 2011D RothHeating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 18 for different condit

Page 4

12Roth RXT Series, 14 Nov 2011DHeating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 18 for different condit

Page 5

13RXT Series, 14 Nov 2011D RothHeating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 18 for different condit

Page 6 - Two-Stage Packaged Units

14Roth RXT Series, 14 Nov 2011DEWT Flow Air1ow HC HE LAT COP DH Air1ow TC SC HR EER DH°F GPM PSI FT CFM MBtuh MBtuh °F W/W MBtuh CFM MBtuh MBtuh MBtuh

Page 7

15RXT Series, 14 Nov 2011D RothEWT Flow Air1ow HC HE LAT COP DH Air1ow TC SC HR EER DH°F GPM PSI FT CFM MBtuh MBtuh °F W/W MBtuh CFM MBtuh MBtuh MBtuh

Page 8

16Roth RXT Series, 14 Nov 2011D(:7 )ORZ $LURZ +& +( /$7 &23 '+ $LURZ 7& 6& +5 ((5 '+) *30 36, )7 &)0 0%WXK 0%WXK ) :

Page 9

17RXT Series, 14 Nov 2011D RothEWT Flow Air1ow HC HE LAT COP DH Air1ow TC SC HR EER DH°F GPM PSI FT CFM MBtuh MBtuh °F W/W MBtuh CFM MBtuh MBtuh MBtuh

Page 10 - Roth RXT Series, 14 Nov 2011D

18Roth RXT Series, 14 Nov 2011DHeating Correction Factors - Full LoadCooling Correction Factors Sensible Cooling Correction FactorsEAT °F HC HE kW50 1

Page 11 - RXT Series, 14 Nov 2011D Roth

19RXT Series, 14 Nov 2011D RothSection 7: Installation IntroductionINTRODUCTION:This geothermal heat pump provides heating and cooling as well as opti

Page 12

2Roth RXT Series, 14 Nov 2011DSection 1: Model Nomenclature

Page 13

20Roth RXT Series, 14 Nov 2011D4. Verify that all refrigerant tubing is free of dents and kinks. Refrigerant tubing should not be touching other unit

Page 14

21RXT Series, 14 Nov 2011D RothConsumer Instructions: Dealer should instruct the consumer in proper operation, maintenance, fi lter replacements, therm

Page 15

22Roth RXT Series, 14 Nov 2011DSection 9a: Unit PlacementUNIT PLACEMENT:When installing a geothermal heating and cooling unit, there are several items

Page 16

23RXT Series, 14 Nov 2011D RothSection 9b: Unit ConversionUNIT CONVERSION:Units are shipped in the left hand return air, upfl ow confi guration. The con

Page 17

24Roth RXT Series, 14 Nov 2011DDUCT WORK:All new ductwork shall be designed as outlined in Sheet Metal and Air Conditioning Contractors National Assoc

Page 18

25RXT Series, 14 Nov 2011D RothSection 9c: Ductwork Installation$FFHVVLEOH)LOWHU5DFN+HDW3XPS)OH[&RQQHFWRU5HWXUQ$LU)OH[&RQQHFWRU6XSSO\$LU

Page 19 - ঑CAUTION ঑

26Roth RXT Series, 14 Nov 2011DOpen Loop PipingPlacement of the components for an open loop system are important when considering water quality and lo

Page 20 - ঑WARNING ঑

27RXT Series, 14 Nov 2011D RothWater QualityThe quality of the water used in geothermal systems is very important. In closed loop systems the dilution

Page 21

28Roth RXT Series, 14 Nov 2011DSection 10: Unit Piping InstallationInterior PipingAll interior piping must be sized for proper fl ow rates and pressure

Page 22 - ঑NOTICE ঑

29RXT Series, 14 Nov 2011D RothTypical Non-Pressurized Flow Center InstallationStanding column fl ow centers are designed to operate with no static pre

Page 23 - Figure 1: Unit Conversion

3RXT Series, 14 Nov 2011D RothGround Loop Heat PumpGround Water Heat PumpNote: Rated in accordance with ISO Standard 13256-1 which includes Pump Penal

Page 24

30Roth RXT Series, 14 Nov 2011DCondensation Drain ConnectionConnect the EZ-Trap to the condensate drain on the equipment drain connection. The condens

Page 25

31RXT Series, 14 Nov 2011D RothAntifreeze Overview In areas where minimum entering loop temperatures drop below 40°F, or where piping will be routed t

Page 26 - HEAT PUMP

32Roth RXT Series, 14 Nov 2011DNotes: 1. Consult with your representative or distributor if you have any questions regarding antifreeze selection or

Page 27 - Table 2: Water Quality

33RXT Series, 14 Nov 2011D RothTable 5: Antifreeze Percentages by Volume0.9600 0.9700 0.9800 0.9900 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 -5 0

Page 28 - Table 3: Pipe Insulation

34Roth RXT Series, 14 Nov 2011DCONTENTS OF THE DESUPERHEATER FITTING KIT,P/N 11080008001: • (1) p/n 23-23-0024-001, Installation Instructions • (1)

Page 29

35RXT Series, 14 Nov 2011D Roth15. Shut off the valve installed in the desuperheater line close to the tee in the cold water line. Open the air vent

Page 30

36Roth RXT Series, 14 Nov 2011DFigure 11: Typical Desuperheater InstallationSection 12: Desuperheater InstallationFigure 12: Desuperheater Installatio

Page 31 - Section 11: Antifreeze

37RXT Series, 14 Nov 2011D RothMICROPROCESSOR FEATURES AND OPERATION Roth geothermal heat pump controls provide a unique modular approach for controll

Page 32

38Roth RXT Series, 14 Nov 2011DSafety Controls The control receives separate signals for high pressure, low pressure, low water fl ow, and condensate o

Page 33

39RXT Series, 14 Nov 2011D RothDiagnostics The lockout board includes fi ve LEDs (status, high pressure, low pressure, low water fl ow, condensate overfl

Page 34

4Roth RXT Series, 14 Nov 2011DSection 3a: Unit Dimensional DataModelDimensional Datawithout Control BoxDimensional Datawith Control BoxSupply Air(Top

Page 35

40Roth RXT Series, 14 Nov 2011DSection 13: ControlsFigure 14: Lockout Board LayoutACRYLOCCGCCHPHPLPLPFSFSCOCOLockoutBoardStatusR2 R1 C2 C1WSDTES

Page 36 - Connection Detail

41RXT Series, 14 Nov 2011D RothSection 13: ControlsTable 7: ECM Fan Performance - Two-Stage Compressor UnitsECM Fan Performance - Two-Stage Compresso

Page 37 - Section 13: Controls

42Roth RXT Series, 14 Nov 2011DSection 13: Controls

Page 38 - Figure 13: ECM Board Layout

43RXT Series, 14 Nov 2011D RothTable 9: Auxiliary Heater Electrical DataInstalling Electric Heater High Voltage Wires:All wiring MUST be done in stric

Page 39 - Table 6: LED Identifi cation

44Roth RXT Series, 14 Nov 2011D+-DCBridgeLEDDiodeRY124VAC input from unit #1+-DiodeRY224VAC input from unit #2RY1RY2240VAC input240VAC to pump(s)24VAC

Page 40

45RXT Series, 14 Nov 2011D RothPERFORMANCE CHECKHeat of Extraction(HE)/Rejection(HR)Record information on the Unit Start-up FormEquipment should be in

Page 41

46Roth RXT Series, 14 Nov 2011DSection 15: TroubleshootingA: UNIT WILL NOT START IN EITHER CYCLEThermostatSet thermostat on heating and highest temper

Page 42

47RXT Series, 14 Nov 2011D RothSection 15: TroubleshootingF: NO WATER FLOWPump ModuleMake sure Pump Module is connected to the control box relay (chec

Page 43 - Section 14: Accessories

48Roth RXT Series, 14 Nov 2011D&KHFNIRUSURSHUFRPSUHVVRUQDPHSODWHYROWDJH$WWHPSWWRUHVWDUWWKHFRPSUHVVRU2.$OORZWRVWDUWWKHFRPSUHVVRUZKLOH

Page 44

49RXT Series, 14 Nov 2011D RothSection 15: TroubleshootingTable 15: Refrigeration TroubleshootingSystem Faults ModeDischargePressureSuctionPressureSup

Page 45 - Section 15: Troubleshooting

5RXT Series, 14 Nov 2011D RothSection 3b: Unit Physical DataDual Capacity Vertical Model Number

Page 46

50Roth RXT Series, 14 Nov 2011D

Page 47

51RXT Series, 14 Nov 2011D RothTo suction line bulbTo suction lineAir CoilSuctionCoaxDischargeHeatingModeAir CoilSuctionCoaxDischargeCoolingModeLiquid

Page 49

Cut along this lineEQUIPMENT START-UP FORMCustomer Name:_________________________________________________________________ Customer Address:___________

Page 50

Equipment Start-Up Process Check the following before power is applied to the equipment Caution: Do not start-up the unit until the new structure is

Page 51 - Cut along this line

STANDARD RESIDENTIAL WARRANTY Roth Industries, Inc. for brand: “TerraStar” Residential Single Family 10 YEAR LIMITED WA

Page 52

OPTIONAL WARRANTY Roth Industries, Inc. for brand: “TerraStar” Residential Single Family 5 YEAR LIMITED WARRANTY (5/5/5) Roth Industries, Inc. Off

Page 53

6Roth RXT Series, 14 Nov 2011DSection 4: Unit Electrical DataTwo-Stage Packaged UnitsModelVoltageCode60Hz Power CompressorECMFan MotorFLAHWGPumpFLAExt

Page 54

7RXT Series, 14 Nov 2011D RothWater Flow SelectionProper fl ow rate is crucial for reliable operation of geothermal heat pumps. The performance data s

Page 55 - Section 17: Warranty

8Roth RXT Series, 14 Nov 2011DHeating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 18 for different conditi

Page 56

9RXT Series, 14 Nov 2011D RothHeating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 18 for different conditi